Bipolar Current Pulse Output (IAD) Modul

   Picture IAD       Picture IAD   

Baer Bipolar Current Outputs deliver a constant 24V DC, but with a polarity change with each meter pulse.

This provides what amounts to an extra power supply, that is usually used to supply power to other Bipolar Current Outputs from the same unit. This means that individual connection terminals from different Bipolar Current Outputs must be isolated from each other, even if other equipment is connected in-between these terminals. Any Bipolar Current Inputs that come afterwards, must be isolated.




Functional block diagram

Functional block diagram IAD
IAD aktive



Pin assignment and package outline

Pin assignment IAD  
left
 
1  NA
2  IN +  
3  UCC
4  GND / IN –
 rechts 
 
1  UDD (+)
2  USS (–)
3  OUT
4  OUT



Recommended operating conditions and electrical characteristics

Galvanic isolation of input and output     yes
Voltage proof   > 4 kV
 
     MIN       TYP       MAX      UNIT  
Input:        
UCC 5 15 V (DC)
ICC 3 mA
Iin 500 µA
Output:        
UDD 24 30 V (DC)
Imax 50 mA
Uout 21   V (bei 30mA)  
fout 100 Hz
Input complies with CMOS-Specifications